Parameters of standard FRP centrifugal fan

  • Fan type JTF-5C
  • Applicable air volume 3031-11517(m³/h)
  • Applicable wind pressure 510-2148(Pa)
  • Applicable revolutions 1200-1900(rpm)
  • Applicable power 1.1-7.3(Kw)
  • Fan weight (excluding motor)
  • Applicable working temperature

      -20℃~60℃(Standard)

    -20℃~100℃(High temperature)

  • Outline size

    AB:1174*970*1135

    CD:1174*970*1106

    EF:1309*970*1055

    KL:1427*970*1048

  • Model annotation
  • How to select
  • Precautions for fan installation
  • Fan maintenance manual

JTF-5C 型号注解.jpg

1. Selection process

image.png 

2. Selection content

(1) Air volume: determined by the air volume required by the system;

(2)Total pressure: determined by the resistance of pipeline system and equipment;

(3) Angle of inlet and outlet: determined by the direction of inlet and outlet;

(4) Optional direction: determined by the pipeline system;

(5) Transmission mode: determine the transmission efficiency. The mechanical efficiency of the direct drive of the motor, the direct drive of the coupling and the belt drive are 1, 0.98 and 0.95 respectively.

(6) When selecting the fan, the air leakage and resistance calculation error due to the lax ventilation pipe system shall be considered. In order to make the fan operate reliably, the air volume and pressure of the system shall be reserved.

Air volume and air pressure margin selection table


Air supply and exhaust system

Air leakage

Additional resistance of pipe network

General air supply and exhaust system

5%-10%

10%-15%

Dust removal system

10%-15%

15%-20%

Boiler blower system

5%-10%

10%-15%

    Precautions for fan installation


  1. Determine the rationality of the installation position and select the correct installation size.

  2. All bolt holes on the air duct support shall be drilled, and gas welding is not allowed.

  3. On the basis of correctly fixing the fan, the vibration of the fan will be increased due to the pollution during the rotation of the fan, so it is necessary to use bolts of appropriate size to fix the fan on the basis of planning to fix the fan.

  4. When installing the shockproof pad, the shockproof pad shall be installed on the fan first, and then the position of the bolt hole shall be drawn on this basis, so as to prevent the rubber of the shockproof pad from being forced and twisted.

  5. After the fan is fixed, the anchor bolt hole of secondary grouting is required. Pea stone concrete should be used for secondary grouting, and cement mortar should not be used to pour holes.

    Fan maintenance manual


  1. The fan shall be stored in a dry and ventilated indoor place to prevent the motor from getting damp; the fan stored in the open air shall be provided with protective measures to prevent rainwater and other sundries from entering the fan.

  2. For fans that have been stored for a long time, the rotating parts of the fans shall be derusted every month and coated with antirust oil to prevent rusting.

  3. The fan blades shall be cleaned regularly to extend the service life of the fan.

  4. Before starting the fan, make sure that the ventilation device at the inlet and outlet of the ventilation system is in the open state, so as to avoid the fan motor being burned due to the long-term back pressure.

  5. In case of abnormal sound, serious heating of motor, electrified shell, tripping of switch, etc. during the operation of the fan, the fan shall be shut down immediately for inspection. Restart the machine after confirming that there is no error.

  6. The use environment of the fan should always be kept clean, the surface of the fan should be kept clean, the inlet and outlet of the ventilation system should be free of sundries, and the dust and other sundries in the fan and the pipeline should be removed regularly. If there is an air filter, it should be cleaned regularly.

  7. According to the use environment and the actual situation, supplement or replace the wet wheel grease for the bearing irregularly.

Installation diagram Please click to download the detailed size drawing

Pay attention to the public number Get the extraction code.

0001.jpg

Fan performance selection parameter table

JTF-5CP=1.2kg/m3T=20℃
Pa12511233119611421070979871744.71450rpm
m3/h36624395512758596592732480578789
Kw2.0 2.2 2.4 2.6 2.8 3.0 3.1 3.3 
Pa214821172054196118361681149512791900rpm
m3/h4799575867187678863895971055711517
Kw4.4 4.9 5.4 5.8 6.3 6.6 7.0 7.3 
Pa192819001843175916481509134211481800rpm
m3/h4546545563647274818390921000110911
Kw3.8 4.2 4.6 5.0 5.3 5.6 6.0 6.2 
Pa172016951644157014701346119710241700rpm
m3/h429451526011687077288587944610304
Kw3.2 3.5 3.9 5.2 4.5 4.7 5.0 5.2 
Pa15241501145713901302119210619061600rpm
m3/h40414849565764667274808288909698
Kw2.6 2.9 3.2 3.5 3.7 3.9 4.2 4.4 
Pa1339131912801222114510489327971500rpm
m3/h37884546530460616819757783349092
Kw2.2 2.4 2.6 2.8 3.1 3.2 3.4 3.6 
Pa11661149111510659979128116941400rpm
m3/h35364243495056576364707277798486
Kw1.7 1.9 2.1 2.3 2.5 2.6 2.8 2.9 
Pa10069909619178597877005981300rpm
m3/h32833940459752535910656772237880
Kw1.4 1.5 1.7 1.8 2.0 2.1 2.2 2.3 
Pa8578448197827326705965101200rpm
m3/h30313637424348495455606166687274
Kw1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 