Parameters of standard FRP centrifugal fan

  • Fan type JTF-9C
  • Applicable air volume 11690-36745(m³/h)
  • Applicable wind pressure 1158-3337(Pa)
  • Applicable revolutions 1130-1480(rpm)
  • Applicable power 9.9-36.6(Kw)
  • Fan weight (excluding motor)
  • Applicable working temperature

      -20℃~60℃(Standard)

    -20℃~100℃(High temperature)

  • Outline size

    AB:1881.5*1520*1890

    CD:1881.5*1520*1845

    EF:2131.5*1520*1740

    KL:2327.5*1520*1749

  • Model annotation
  • How to select
  • Precautions for fan installation
  • Fan maintenance manual

JTF-9C 型号注解.jpg

1. Selection process

image.png 

2. Selection content

(1) Air volume: determined by the air volume required by the system;

(2)Total pressure: determined by the resistance of pipeline system and equipment;

(3) Angle of inlet and outlet: determined by the direction of inlet and outlet;

(4) Optional direction: determined by the pipeline system;

(5) Transmission mode: determine the transmission efficiency. The mechanical efficiency of the direct drive of the motor, the direct drive of the coupling and the belt drive are 1, 0.98 and 0.95 respectively.

(6) When selecting the fan, the air leakage and resistance calculation error due to the lax ventilation pipe system shall be considered. In order to make the fan operate reliably, the air volume and pressure of the system shall be reserved.

Air volume and air pressure margin selection table


Air supply and exhaust system

Air leakage

Additional resistance of pipe network

General air supply and exhaust system

5%-10%

10%-15%

Dust removal system

10%-15%

15%-20%

Boiler blower system

5%-10%

10%-15%

    Precautions for fan installation


  1. Determine the rationality of the installation position and select the correct installation size.

  2. All bolt holes on the air duct support shall be drilled, and gas welding is not allowed.

  3. On the basis of correctly fixing the fan, the vibration of the fan will be increased due to the pollution during the rotation of the fan, so it is necessary to use bolts of appropriate size to fix the fan on the basis of planning to fix the fan.

  4. When installing the shockproof pad, the shockproof pad shall be installed on the fan first, and then the position of the bolt hole shall be drawn on this basis, so as to prevent the rubber of the shockproof pad from being forced and twisted.

  5. After the fan is fixed, the anchor bolt hole of secondary grouting is required. Pea stone concrete should be used for secondary grouting, and cement mortar should not be used to pour holes.

    Fan maintenance manual


  1. The fan shall be stored in a dry and ventilated indoor place to prevent the motor from getting damp; the fan stored in the open air shall be provided with protective measures to prevent rainwater and other sundries from entering the fan.

  2. For fans that have been stored for a long time, the rotating parts of the fans shall be derusted every month and coated with antirust oil to prevent rusting.

  3. The fan blades shall be cleaned regularly to extend the service life of the fan.

  4. Before starting the fan, make sure that the ventilation device at the inlet and outlet of the ventilation system is in the open state, so as to avoid the fan motor being burned due to the long-term back pressure.

  5. In case of abnormal sound, serious heating of motor, electrified shell, tripping of switch, etc. during the operation of the fan, the fan shall be shut down immediately for inspection. Restart the machine after confirming that there is no error.

  6. The use environment of the fan should always be kept clean, the surface of the fan should be kept clean, the inlet and outlet of the ventilation system should be free of sundries, and the dust and other sundries in the fan and the pipeline should be removed regularly. If there is an air filter, it should be cleaned regularly.

  7. According to the use environment and the actual situation, supplement or replace the wet wheel grease for the bearing irregularly.

Installation diagram Please click to download the detailed size drawing

Pay attention to the public number Get the extraction code.

0001.jpg

Fan performance selection parameter table

JTF-9CP=1.2kg/m3T=20℃
Pa320331563063292327382507223019071450rpm
m3/h1500018000210002400027000300003300036000
Kw20.9 23.2 25.4 27.4 29.3 31.2 32.9 34.4 
Pa333732883191304628532612232319861480rpm
m3/h1531018372214342449727559306213368336745
Kw22.2 24.7 27.0 29.2 31.2 33.1 34.9 36.6 
Pa311530692979284326632438216918541430rpm
m3/h1479317752207102366926628295863254535503
Kw20.0 22.2 24.3 26.3 28.1 29.9 31.5 33.0 
Pa290128592774264824802271202017271380rpm
m3/h1427617131199862284125697285523140734262
Kw18.0 20.0 21.9 23.6 25.3 26.9 28.3 29.7 
Pa269526552577246023042109187616041330rpm
m3/h1375916510192622201324766275173026933021
Kw16.1 17.9 19.6 21.1 22.6 24.0 25.3 26.6 
Pa249624592387227821341954173814861280rpm
m3/h1324115890185382118623834264832913131779
Kw14.4 15.9 17.4 18.8 20.2 21.4 22.6 23.7 
Pa230522712204210419701804160413721230rpm
m3/h1272415269178142035922903254482799330538
Kw12.7 14.1 15.5 16.7 17.9 19.0 20.0 21.0 
Pa212120902028193618131660147712631180rpm
m3/h1220714648170901953121972244142685529297
Kw11.2 12.5 13.6 14.7 15.8 16.8 17.7 18.5 
Pa194519171860177516631522135411581130rpm
m3/h1169014028163661870321041233792571728055
Kw9.9 10.9 12.0 12.9 13.9 14.7 15.5 16.3 