Parameters of standard FRP centrifugal fan

  • Fan type JTF-6C
  • Applicable air volume 4670-18539
  • Applicable wind pressure 584-1801(Pa)
  • Applicable revolutions 1070-1770(rpm)
  • Applicable power 1.9-14.8(Kw)
  • Fan weight (excluding motor)
  • Applicable working temperature

      -20℃~60℃(Standard)

    -20℃~100℃(High temperature)

  • Outline size

    AB:1484*1148*1395

    CD:1484*1148*1360

    EF:1629*1148*1320

    KL:1794*1148*1295

  • Model annotation
  • How to select
  • Precautions for fan installation
  • Fan maintenance manual

JTF-6C 型号注解.jpg

1. Selection process

image.png 

2. Selection content

(1) Air volume: determined by the air volume required by the system;

(2)Total pressure: determined by the resistance of pipeline system and equipment;

(3) Angle of inlet and outlet: determined by the direction of inlet and outlet;

(4) Optional direction: determined by the pipeline system;

(5) Transmission mode: determine the transmission efficiency. The mechanical efficiency of the direct drive of the motor, the direct drive of the coupling and the belt drive are 1, 0.98 and 0.95 respectively.

(6) When selecting the fan, the air leakage and resistance calculation error due to the lax ventilation pipe system shall be considered. In order to make the fan operate reliably, the air volume and pressure of the system shall be reserved.

Air volume and air pressure margin selection table


Air supply and exhaust system

Air leakage

Additional resistance of pipe network

General air supply and exhaust system

5%-10%

10%-15%

Dust removal system

10%-15%

15%-20%

Boiler blower system

5%-10%

10%-15%

    Precautions for fan installation


  1. Determine the rationality of the installation position and select the correct installation size.

  2. All bolt holes on the air duct support shall be drilled, and gas welding is not allowed.

  3. On the basis of correctly fixing the fan, the vibration of the fan will be increased due to the pollution during the rotation of the fan, so it is necessary to use bolts of appropriate size to fix the fan on the basis of planning to fix the fan.

  4. When installing the shockproof pad, the shockproof pad shall be installed on the fan first, and then the position of the bolt hole shall be drawn on this basis, so as to prevent the rubber of the shockproof pad from being forced and twisted.

  5. After the fan is fixed, the anchor bolt hole of secondary grouting is required. Pea stone concrete should be used for secondary grouting, and cement mortar should not be used to pour holes.

    Fan maintenance manual


  1. The fan shall be stored in a dry and ventilated indoor place to prevent the motor from getting damp; the fan stored in the open air shall be provided with protective measures to prevent rainwater and other sundries from entering the fan.

  2. For fans that have been stored for a long time, the rotating parts of the fans shall be derusted every month and coated with antirust oil to prevent rusting.

  3. The fan blades shall be cleaned regularly to extend the service life of the fan.

  4. Before starting the fan, make sure that the ventilation device at the inlet and outlet of the ventilation system is in the open state, so as to avoid the fan motor being burned due to the long-term back pressure.

  5. In case of abnormal sound, serious heating of motor, electrified shell, tripping of switch, etc. during the operation of the fan, the fan shall be shut down immediately for inspection. Restart the machine after confirming that there is no error.

  6. The use environment of the fan should always be kept clean, the surface of the fan should be kept clean, the inlet and outlet of the ventilation system should be free of sundries, and the dust and other sundries in the fan and the pipeline should be removed regularly. If there is an air filter, it should be cleaned regularly.

  7. According to the use environment and the actual situation, supplement or replace the wet wheel grease for the bearing irregularly.

Installation diagram Please click to download the detailed size drawing

Pay attention to the public number Get the extraction code.

0001.jpg

Fan performance selection parameter table

JTF-6CP=1.2kg/m3T=20℃
Pa180117751723164415401410125410721450rpm
m3/h6328759488591012511391126561392215188
Kw4.9 5.5 6.0 6.5 6.9 7.4 7.8 8.1 
Pa268526452567245022952101186915981770rpm
m3/h77259270108151235913904154491699418539
Kw9.0 10.0 10.9 11.8 12.6 13.4 14.2 14.8 
Pa239023552285218120431870166414231670rpm
m3/h72888746102041166113119145771603417492
Kw7.5 8.4 9.2 9.9 10.6 11.3 11.9 12.5 
Pa211220812020192818061653147012571570rpm
m3/h6851822295931096312333137041507416444
Kw6.3 7.0 7.6 8.2 8.8 9.4 9.9 10.3 
Pa185118251771169015821449128911021470rpm
m3/h6415769889821026511548128311411415397
Kw5.1 5.7 6.2 6.7 7.2 7.7 8.1 8.5 
Pa16081585153814681375125911209571370rpm
m3/h597871758371956610762119581315414350
Kw4.1 4.6 5.0 5.4 5.8 6.2 6.5 6.9 
Pa1382136213221261118210829628221270rpm
m3/h55426651776088689977110851219413302
Kw3.3 3.7 4.0 4.3 4.6 4.9 5.2 5.4 
Pa117311561122107110039188176981170rpm
m3/h51066127714981709191102121123412255
Kw2.6 2.8 3.1 3.4 3.6 3.8 4.1 4.2 
Pa9819679388958387676835841070rpm
m3/h4670560465387472840593391027311207
Kw1.9 2.2 2.4 2.6 2.8 2.9 3.1 3.2 