中文  |  English

Parameters of standard FRP centrifugal fan

  • Fan type GYF-10C
  • Applicable air volume 8826-21757(m³/h)
  • Applicable wind pressure 2369-5493(Pa)
  • Applicable revolutions 1450-1800(rpm)
  • Applicable power 14.6-39.4(Kw)
  • Fan weight (excluding motor)
  • Applicable working temperature

      -20℃~60℃(Standard)

    -20℃~100℃(High temperature)

  • Outline size

    AB:2568*1914*2476

    CD:2568*1914*2336

    E向:2478*1914*2296

  • Model annotation
  • How to select
  • Precautions for fan installation
  • Fan maintenance manual

GYF-10C 型号注解.jpg

1. Selection process

image.png 

2. Selection content

(1) Air volume: determined by the air volume required by the system;

(2)Total pressure: determined by the resistance of pipeline system and equipment;

(3) Angle of inlet and outlet: determined by the direction of inlet and outlet;

(4) Optional direction: determined by the pipeline system;

(5) Transmission mode: determine the transmission efficiency. The mechanical efficiency of the direct drive of the motor, the direct drive of the coupling and the belt drive are 1, 0.98 and 0.95 respectively.

(6) When selecting the fan, the air leakage and resistance calculation error due to the lax ventilation pipe system shall be considered. In order to make the fan operate reliably, the air volume and pressure of the system shall be reserved.

Air volume and air pressure margin selection table


Air supply and exhaust system

Air leakage

Additional resistance of pipe network

General air supply and exhaust system

5%-10%

10%-15%

Dust removal system

10%-15%

15%-20%

Boiler blower system

5%-10%

10%-15%

    Precautions for fan installation


  1. Determine the rationality of the installation position and select the correct installation size.

  2. All bolt holes on the air duct support shall be drilled, and gas welding is not allowed.

  3. On the basis of correctly fixing the fan, the vibration of the fan will be increased due to the pollution during the rotation of the fan, so it is necessary to use bolts of appropriate size to fix the fan on the basis of planning to fix the fan.

  4. When installing the shockproof pad, the shockproof pad shall be installed on the fan first, and then the position of the bolt hole shall be drawn on this basis, so as to prevent the rubber of the shockproof pad from being forced and twisted.

  5. After the fan is fixed, the anchor bolt hole of secondary grouting is required. Pea stone concrete should be used for secondary grouting, and cement mortar should not be used to pour holes.

    Fan maintenance manual


  1. The fan shall be stored in a dry and ventilated indoor place to prevent the motor from getting damp; the fan stored in the open air shall be provided with protective measures to prevent rainwater and other sundries from entering the fan.

  2. For fans that have been stored for a long time, the rotating parts of the fans shall be derusted every month and coated with antirust oil to prevent rusting.

  3. The fan blades shall be cleaned regularly to extend the service life of the fan.

  4. Before starting the fan, make sure that the ventilation device at the inlet and outlet of the ventilation system is in the open state, so as to avoid the fan motor being burned due to the long-term back pressure.

  5. In case of abnormal sound, serious heating of motor, electrified shell, tripping of switch, etc. during the operation of the fan, the fan shall be shut down immediately for inspection. Restart the machine after confirming that there is no error.

  6. The use environment of the fan should always be kept clean, the surface of the fan should be kept clean, the inlet and outlet of the ventilation system should be free of sundries, and the dust and other sundries in the fan and the pipeline should be removed regularly. If there is an air filter, it should be cleaned regularly.

  7. According to the use environment and the actual situation, supplement or replace the wet wheel grease for the bearing irregularly.

Installation diagram Please click to download the detailed size drawing

Pay attention to the public number Get the extraction code.

001.png

002.png

Fan performance selection parameter table

GYF-10CP=1.2kg/m3T=20℃
Pa549355865463519446554165365036501800rpm
m3/h1095713304156521737419252205832175721757
Kw27.9 34.4 35.5 37.4 38.3 38.7 39.4 39.4 
Pa519252805164490944003937345034501750rpm
m3/h1065212935152171689118717200112115221152
Kw25.6 31.6 33.6 34.9 35.2 35.9 36.2 36.2 
Pa461646944591436439113500306730671650rpm
m3/h1004312196143481592617648188671994319943
Kw21.5 26.5 28.1 28.8 29.1 29.6 30.1 30.6 
Pa434044134317410436783291288428841600rpm
m3/h973911826139131544317113182961933919339
Kw19.6 22.3 25.7 26.1 26.5 27.0 27.2 27.7 
Pa407341424051385134523088270727071550rpm
m3/h943511457134781496116578177241873518735
Kw17.8 22.0 23.3 23.9 24.5 24.9 25.6 25.6 
Pa381538793794360732332892253525351500rpm
m3/h913011087130431447816043171521813018130
Kw16.1 19.9 20.5 21.7 22.2 23.0 24.6 24.6 
Pa356536253545337030212703236923691450rpm
m3/h882610717126091399615509165801752617526
Kw14.6 18.0 19.4 19.0 19.4 20.1 20.6 20.6 


image.png