glass fiber reinforced plastic high-pressure isolating box fan glass fiber reinforced plastic high-pressure isolating box fan

Parameters of standard FRP centrifugal fan

  • Fan type GYF-3A
  • Applicable air volume 755-3323(m³/h)
  • Applicable wind pressure 354-1880(Pa)
  • Applicable revolutions 1600-3150(rpm)
  • Applicable power 0.23-2.47(Kw)
  • Fan weight (excluding motor)
  • Applicable working temperature

      -20℃~60℃(Standard)

    -20℃~100℃(High temperature)

  • Outline size

    AB:900*901*943

    CD:900*901*863

     EF:900*901*963

  • Model annotation
  • How to select
  • Precautions for fan installation
  • Fan maintenance manual

GYF-3A 型号注解.jpg

1. Selection process

image.png 

2. Selection content

(1) Air volume: determined by the air volume required by the system;

(2)Total pressure: determined by the resistance of pipeline system and equipment;

(3) Angle of inlet and outlet: determined by the direction of inlet and outlet;

(4) Optional direction: determined by the pipeline system;

(5) Transmission mode: determine the transmission efficiency. The mechanical efficiency of the direct drive of the motor, the direct drive of the coupling and the belt drive are 1, 0.98 and 0.95 respectively.

(6) When selecting the fan, the air leakage and resistance calculation error due to the lax ventilation pipe system shall be considered. In order to make the fan operate reliably, the air volume and pressure of the system shall be reserved.

Air volume and air pressure margin selection table


Air supply and exhaust system

Air leakage

Additional resistance of pipe network

General air supply and exhaust system

5%-10%

10%-15%

Dust removal system

10%-15%

15%-20%

Boiler blower system

5%-10%

10%-15%

    Precautions for fan installation


  1. Determine the rationality of the installation position and select the correct installation size.

  2. All bolt holes on the air duct support shall be drilled, and gas welding is not allowed.

  3. On the basis of correctly fixing the fan, the vibration of the fan will be increased due to the pollution during the rotation of the fan, so it is necessary to use bolts of appropriate size to fix the fan on the basis of planning to fix the fan.

  4. When installing the shockproof pad, the shockproof pad shall be installed on the fan first, and then the position of the bolt hole shall be drawn on this basis, so as to prevent the rubber of the shockproof pad from being forced and twisted.

  5. After the fan is fixed, the anchor bolt hole of secondary grouting is required. Pea stone concrete should be used for secondary grouting, and cement mortar should not be used to pour holes.

    Fan maintenance manual


  1. The fan shall be stored in a dry and ventilated indoor place to prevent the motor from getting damp; the fan stored in the open air shall be provided with protective measures to prevent rainwater and other sundries from entering the fan.

  2. For fans that have been stored for a long time, the rotating parts of the fans shall be derusted every month and coated with antirust oil to prevent rusting.

  3. The fan blades shall be cleaned regularly to extend the service life of the fan.

  4. Before starting the fan, make sure that the ventilation device at the inlet and outlet of the ventilation system is in the open state, so as to avoid the fan motor being burned due to the long-term back pressure.

  5. In case of abnormal sound, serious heating of motor, electrified shell, tripping of switch, etc. during the operation of the fan, the fan shall be shut down immediately for inspection. Restart the machine after confirming that there is no error.

  6. The use environment of the fan should always be kept clean, the surface of the fan should be kept clean, the inlet and outlet of the ventilation system should be free of sundries, and the dust and other sundries in the fan and the pipeline should be removed regularly. If there is an air filter, it should be cleaned regularly.

  7. According to the use environment and the actual situation, supplement or replace the wet wheel grease for the bearing irregularly.

Installation diagram Please click to download the detailed size drawing

Pay attention to the public number Get the extraction code.

004.png

Fan performance selection parameter table

GYF-3AP=1.2kg/m3T=20℃
Pa18801831177217031615150713763150rpm
m3/h1487179320992405271130173323
Kw1.51 1.70 1.88 2.04 2.19 2.35 2.47 
Pa14831445139813441274118910862800rpm
m3/h1322159418662138241026822954
Kw1.14 1.29 1.32 1.43 1.54 1.65 1.74 
Pa118111511114107010159478652500rpm
m3/h1180142316661909215223952637
Kw0.81 0.92 1.01 1.10 1.18 1.26 1.33 
Pa9489238938598147606942240rpm
m3/h1057127514931710192821462363
Kw0.62 0.71 0.73 0.79 0.85 0.91 0.96 
Pa7557357126846496055532000rpm
m3/h944113813331527172119162110
Kw0.44 0.50 0.55 0.60 0.65 0.69 0.73 
Pa6115805765545254904481800rpm
m3/h850119912041374154917241899
Kw0.32 0.37 0.40 0.44 0.47 0.50 0.53 
Pa4834704554374153873541600rpm
m3/h75591110661222137715331688
Kw0.23 0.26 0.28 0.31 0.33 0.35 0.37 


image.png

Last article: GYF-3A高压玻璃钢隔音箱风机
Next article:None