Parameters of standard FRP centrifugal fan

  • Fan type ZYF-8C
  • Applicable air volume 15633-27475(m³/h)
  • Applicable wind pressure 1311-2536(Pa)
  • Applicable revolutions 1180-1660(rpm)
  • Applicable power 13.4-24.2(Kw)
  • Fan weight (excluding motor)
  • Applicable working temperature

      -20℃~60℃(Standard)

    -20℃~100℃(High temperature)

  • Outline size

    AB:1770*1410*2020

    CD:1770*1410*1979

    EF: 2080*1410*1860

    KL: 2258*1410*1764

  • Model annotation
  • How to select
  • Precautions for fan installation
  • Fan maintenance manual

ZYF-8C 型号注解.jpg

1. Selection process

image.png 

2. Selection content

(1) Air volume: determined by the air volume required by the system;

(2)Total pressure: determined by the resistance of pipeline system and equipment;

(3) Angle of inlet and outlet: determined by the direction of inlet and outlet;

(4) Optional direction: determined by the pipeline system;

(5) Transmission mode: determine the transmission efficiency. The mechanical efficiency of the direct drive of the motor, the direct drive of the coupling and the belt drive are 1, 0.98 and 0.95 respectively.

(6) When selecting the fan, the air leakage and resistance calculation error due to the lax ventilation pipe system shall be considered. In order to make the fan operate reliably, the air volume and pressure of the system shall be reserved.

Air volume and air pressure margin selection table


Air supply and exhaust system

Air leakage

Additional resistance of pipe network

General air supply and exhaust system

5%-10%

10%-15%

Dust removal system

10%-15%

15%-20%

Boiler blower system

5%-10%

10%-15%

    Precautions for fan installation


  1. Determine the rationality of the installation position and select the correct installation size.

  2. All bolt holes on the air duct support shall be drilled, and gas welding is not allowed.

  3. On the basis of correctly fixing the fan, the vibration of the fan will be increased due to the pollution during the rotation of the fan, so it is necessary to use bolts of appropriate size to fix the fan on the basis of planning to fix the fan.

  4. When installing the shockproof pad, the shockproof pad shall be installed on the fan first, and then the position of the bolt hole shall be drawn on this basis, so as to prevent the rubber of the shockproof pad from being forced and twisted.

  5. After the fan is fixed, the anchor bolt hole of secondary grouting is required. Pea stone concrete should be used for secondary grouting, and cement mortar should not be used to pour holes.

    Fan maintenance manual


  1. The fan shall be stored in a dry and ventilated indoor place to prevent the motor from getting damp; the fan stored in the open air shall be provided with protective measures to prevent rainwater and other sundries from entering the fan.

  2. For fans that have been stored for a long time, the rotating parts of the fans shall be derusted every month and coated with antirust oil to prevent rusting.

  3. The fan blades shall be cleaned regularly to extend the service life of the fan.

  4. Before starting the fan, make sure that the ventilation device at the inlet and outlet of the ventilation system is in the open state, so as to avoid the fan motor being burned due to the long-term back pressure.

  5. In case of abnormal sound, serious heating of motor, electrified shell, tripping of switch, etc. during the operation of the fan, the fan shall be shut down immediately for inspection. Restart the machine after confirming that there is no error.

  6. The use environment of the fan should always be kept clean, the surface of the fan should be kept clean, the inlet and outlet of the ventilation system should be free of sundries, and the dust and other sundries in the fan and the pipeline should be removed regularly. If there is an air filter, it should be cleaned regularly.

  7. According to the use environment and the actual situation, supplement or replace the wet wheel grease for the bearing irregularly.

Installation diagram Please click to download the detailed size drawing

Pay attention to the public number Get the extraction code.

0001.jpg

Fan performance selection parameter table

ZYF-8CP=1.2kg/m3T=20℃
Pa283527692689259224782344218920111660rpm
m3/h1936720750221332351724900262832766729050
Kw19.1 20.0 20.7 21.2 21.7 21.9 22.1 22.5 
Pa253624772405231922162097195817991570rpm
m3/h1831719625209332224223550248582616727375
Kw18.8 19.7 20.4 20.9 21.2 21.4 21.7 22.1 
Pa226022012137206119701863174016101480rpm
m3/h1710718500197332096722200234332466725700
Kw15.6 16.4 17.0 17.4 17.6 17.8 18.1 18.2 
Pa204619981940187017881691157914601410rpm
m3/h1625017625188001997521150223252350024445
Kw14.1 14.9 15.5 15.8 16.0 16.3 16.4 16.5 
Pa184818051752168916151527141613111340rpm
m3/h1547516750178671898320100212172233323220
Kw12.6 13.3 13.8 14.1 14.3 14.5 15.4 15.7 
Pa163415951549149314281351126111651260rpm
m3/h1464015750168001785018900199502100021920
Kw9.6 10.1 10.5 10.7 10.9 11.0 11.3 11.8 
Pa143313991359131012521184110610161180rpm
m3/h1376714750157331671717700186831966720650
Kw7.9 8.3 8.6 8.8 9.1 10.2 11.0 11.2 


image.png

Last article:GYF-5C玻璃钢高压防爆风机
Next article:None