Parameters of standard FRP centrifugal fan

  • Fan type GYF-5C
  • Applicable air volume 1591-4684(m3/h)
  • Applicable wind pressure 2397-3670(Pa)
  • Applicable revolutions 2100-2800(rpm)
  • Applicable power 2.4-7.1
  • Fan weight (excluding motor)
  • Applicable working temperature

      -20℃~60℃(Standard)

    -20℃~100℃(High temperature)

  • Outline size

    AB:1210*825*1275

    CD:1210*825*1201

    EF:1310*825*1175

    KL:1446*825*1173

  • Model annotation
  • How to select
  • Precautions for fan installation
  • Fan maintenance manual

GYF-5C 型号注解.jpg

1. Selection process

image.png 

2. Selection content

(1) Air volume: determined by the air volume required by the system;

(2)Total pressure: determined by the resistance of pipeline system and equipment;

(3) Angle of inlet and outlet: determined by the direction of inlet and outlet;

(4) Optional direction: determined by the pipeline system;

(5) Transmission mode: determine the transmission efficiency. The mechanical efficiency of the direct drive of the motor, the direct drive of the coupling and the belt drive are 1, 0.98 and 0.95 respectively.

(6) When selecting the fan, the air leakage and resistance calculation error due to the lax ventilation pipe system shall be considered. In order to make the fan operate reliably, the air volume and pressure of the system shall be reserved.

Air volume and air pressure margin selection table


Air supply and exhaust system

Air leakage

Additional resistance of pipe network

General air supply and exhaust system

5%-10%

10%-15%

Dust removal system

10%-15%

15%-20%

Boiler blower system

5%-10%

10%-15%

    Precautions for fan installation


  1. Determine the rationality of the installation position and select the correct installation size.

  2. All bolt holes on the air duct support shall be drilled, and gas welding is not allowed.

  3. On the basis of correctly fixing the fan, the vibration of the fan will be increased due to the pollution during the rotation of the fan, so it is necessary to use bolts of appropriate size to fix the fan on the basis of planning to fix the fan.

  4. When installing the shockproof pad, the shockproof pad shall be installed on the fan first, and then the position of the bolt hole shall be drawn on this basis, so as to prevent the rubber of the shockproof pad from being forced and twisted.

  5. After the fan is fixed, the anchor bolt hole of secondary grouting is required. Pea stone concrete should be used for secondary grouting, and cement mortar should not be used to pour holes.

    Fan maintenance manual


  1. The fan shall be stored in a dry and ventilated indoor place to prevent the motor from getting damp; the fan stored in the open air shall be provided with protective measures to prevent rainwater and other sundries from entering the fan.

  2. For fans that have been stored for a long time, the rotating parts of the fans shall be derusted every month and coated with antirust oil to prevent rusting.

  3. The fan blades shall be cleaned regularly to extend the service life of the fan.

  4. Before starting the fan, make sure that the ventilation device at the inlet and outlet of the ventilation system is in the open state, so as to avoid the fan motor being burned due to the long-term back pressure.

  5. In case of abnormal sound, serious heating of motor, electrified shell, tripping of switch, etc. during the operation of the fan, the fan shall be shut down immediately for inspection. Restart the machine after confirming that there is no error.

  6. The use environment of the fan should always be kept clean, the surface of the fan should be kept clean, the inlet and outlet of the ventilation system should be free of sundries, and the dust and other sundries in the fan and the pipeline should be removed regularly. If there is an air filter, it should be cleaned regularly.

  7. According to the use environment and the actual situation, supplement or replace the wet wheel grease for the bearing irregularly.

Installation diagram Please click to download the detailed size drawing

Pay attention to the public number Get the extraction code.

GYF-5C-ALL向-模型.png

Fan performance selection parameter table

GYF-5CP=1.2kg/m3T=20℃
Pa367036493597352534213292315230062800rpm
m3/h17822271269830553431383942514684
Kw3.3 4.2 4.9 5.4 5.9 6.4 6.8 7.1 
Pa316431463102303929502838271725922600rpm
m3/h16552108250528363186356439474349
Kw2.6 3.4 3.9 4.4 4.7 5.1 5.4 5.7 
Pa292629092868281027272624251223972500rpm
m3/h15912027240927273064342737954182
Kw2.6 3.3 3.8 4.3 4.6 5.0 5.3 5.6 
Pa269626812643259025132418231522092400rpm
m3/h15271946231326182941329036444015
Kw2.1 2.6 3.1 3.4 3.7 4.0 4.3 4.5 
Pa247624622427237823082221212620292300rpm
m3/h14641865221625092819315334923847
Kw1.8 2.3 2.7 3.0 3.3 3.5 3.8 3.9 
Pa226622532221217621122032194618562200rpm
m3/h14001784212024002696301633403680
Kw1.8 2.2 2.6 2.9 3.2 3.4 3.6 3.8 
Pa206420532023198319241851177316912100rpm
m3/h13361703202422912573287931883513
Kw1.4 1.8 2.1 2.3 2.5 2.7 2.9 3.0 