Parameters of standard FRP centrifugal fan

  • Fan type GYF-11C
  • Applicable air volume 15188-33509(m³/h)
  • Applicable wind pressure 2913-5471(pa)
  • Applicable revolutions 1150-1500(rpm)
  • Applicable power 30.8-63.4(Kw)
  • Fan weight (excluding motor)
  • Applicable working temperature

      -20℃~60℃(Standard)

    -20℃~100℃(High temperature)

  • Outline size

    AB:2313*1570*2515

    CD:2313*1570*2361

    EF:2638*1570*2190

    KL:2891*1570*2145

  • Model annotation
  • How to select
  • Precautions for fan installation
  • Fan maintenance manual

image.png

1. Selection process

image.png 

2. Selection content

(1) Air volume: determined by the air volume required by the system;

(2)Total pressure: determined by the resistance of pipeline system and equipment;

(3) Angle of inlet and outlet: determined by the direction of inlet and outlet;

(4) Optional direction: determined by the pipeline system;

(5) Transmission mode: determine the transmission efficiency. The mechanical efficiency of the direct drive of the motor, the direct drive of the coupling and the belt drive are 1, 0.98 and 0.95 respectively.

(6) When selecting the fan, the air leakage and resistance calculation error due to the lax ventilation pipe system shall be considered. In order to make the fan operate reliably, the air volume and pressure of the system shall be reserved.

Air volume and air pressure margin selection table


Air supply and exhaust system

Air leakage

Additional resistance of pipe network

General air supply and exhaust system

5%-10%

10%-15%

Dust removal system

10%-15%

15%-20%

Boiler blower system

5%-10%

10%-15%

    Precautions for fan installation


  1. Determine the rationality of the installation position and select the correct installation size.

  2. All bolt holes on the air duct support shall be drilled, and gas welding is not allowed.

  3. On the basis of correctly fixing the fan, the vibration of the fan will be increased due to the pollution during the rotation of the fan, so it is necessary to use bolts of appropriate size to fix the fan on the basis of planning to fix the fan.

  4. When installing the shockproof pad, the shockproof pad shall be installed on the fan first, and then the position of the bolt hole shall be drawn on this basis, so as to prevent the rubber of the shockproof pad from being forced and twisted.

  5. After the fan is fixed, the anchor bolt hole of secondary grouting is required. Pea stone concrete should be used for secondary grouting, and cement mortar should not be used to pour holes.

    Fan maintenance manual


  1. The fan shall be stored in a dry and ventilated indoor place to prevent the motor from getting damp; the fan stored in the open air shall be provided with protective measures to prevent rainwater and other sundries from entering the fan.

  2. For fans that have been stored for a long time, the rotating parts of the fans shall be derusted every month and coated with antirust oil to prevent rusting.

  3. The fan blades shall be cleaned regularly to extend the service life of the fan.

  4. Before starting the fan, make sure that the ventilation device at the inlet and outlet of the ventilation system is in the open state, so as to avoid the fan motor being burned due to the long-term back pressure.

  5. In case of abnormal sound, serious heating of motor, electrified shell, tripping of switch, etc. during the operation of the fan, the fan shall be shut down immediately for inspection. Restart the machine after confirming that there is no error.

  6. The use environment of the fan should always be kept clean, the surface of the fan should be kept clean, the inlet and outlet of the ventilation system should be free of sundries, and the dust and other sundries in the fan and the pipeline should be removed regularly. If there is an air filter, it should be cleaned regularly.

  7. According to the use environment and the actual situation, supplement or replace the wet wheel grease for the bearing irregularly.

Installation diagram Please click to download the detailed size drawing

Pay attention to the public number Get the extraction code.

GYF-11C-All向-模型.jpg

Fan performance selection parameter table

GYF-11CP=1.2kg/m3T=20℃
Pa541254715382511745864103359635961500rpm
m3/h1687520491241072675929652317013350933509
Kw42.3 47.9 50.8 51.4 52.5 53.1 55.8 55.8 
Pa505751125029478142853834336033601450rpm
m3/h1631319808233042586728663306443239232392
Kw38.2 43.3 50.1 50.9 51.7 52.2 53.0 53.0 
Pa438344314360414537153324291329131350rpm
m3/h1518818442216962408326687285313015830158
Kw30.8 37.8 38.4 38.8 39.6 39.9 40.7 40.7 
Pa406541094043384334443082270127011300rpm
m3/h1462517759208932319125698274742904129041
Kw27.5 33.8 36.1 36.7 37.3 38.6 39.3 39.3 
Pa375837993738355331852849249724971250rpm
m3/h1406317076200892229924710264172792427924
Kw24.5 30.0 32.1 33.9 35.3 36.1 36.9 36.9 
Pa346335013445327529352626230223021200rpm
m3/h1350016393192862140723721253612680726807
Kw21.6 26.6 30.8 31.9 32.2 33.0 33.6 33.6 
Pa318132163164300826952412211421141150rpm
m3/h1293815710184822051522733243042569025690
Kw19.1 23.4 25.0 26.4 27.0 27.6 28.5 28.5 


image.png

18267014069

(Jiangsu, Zhejiang and Shanghai) 24-hour on-site service