Parameters of standard FRP centrifugal fan

  • Fan type ZYF-4A
  • Applicable air volume 1590-4209(m³/h)
  • Applicable wind pressure 1111-2092(pa)
  • Applicable revolutions 1180-1660(rpm)
  • Applicable power 1.2-2.8(kw)
  • Fan weight (excluding motor)
  • Applicable working temperature

      -20℃~60℃(Standard)

    -20℃~100℃(High temperature)

  • Outline size

    AB:719*758*1078

    CD:719*758*960

    EF:805*758*923

    KL:923*758*932

  • Model annotation
  • How to select
  • Precautions for fan installation
  • Fan maintenance manual

image.png

1. Selection process

image.png 

2. Selection content

(1) Air volume: determined by the air volume required by the system;

(2)Total pressure: determined by the resistance of pipeline system and equipment;

(3) Angle of inlet and outlet: determined by the direction of inlet and outlet;

(4) Optional direction: determined by the pipeline system;

(5) Transmission mode: determine the transmission efficiency. The mechanical efficiency of the direct drive of the motor, the direct drive of the coupling and the belt drive are 1, 0.98 and 0.95 respectively.

(6) When selecting the fan, the air leakage and resistance calculation error due to the lax ventilation pipe system shall be considered. In order to make the fan operate reliably, the air volume and pressure of the system shall be reserved.

Air volume and air pressure margin selection table


Air supply and exhaust system

Air leakage

Additional resistance of pipe network

General air supply and exhaust system

5%-10%

10%-15%

Dust removal system

10%-15%

15%-20%

Boiler blower system

5%-10%

10%-15%

    Precautions for fan installation


  1. Determine the rationality of the installation position and select the correct installation size.

  2. All bolt holes on the air duct support shall be drilled, and gas welding is not allowed.

  3. On the basis of correctly fixing the fan, the vibration of the fan will be increased due to the pollution during the rotation of the fan, so it is necessary to use bolts of appropriate size to fix the fan on the basis of planning to fix the fan.

  4. When installing the shockproof pad, the shockproof pad shall be installed on the fan first, and then the position of the bolt hole shall be drawn on this basis, so as to prevent the rubber of the shockproof pad from being forced and twisted.

  5. After the fan is fixed, the anchor bolt hole of secondary grouting is required. Pea stone concrete should be used for secondary grouting, and cement mortar should not be used to pour holes.

    Fan maintenance manual


  1. The fan shall be stored in a dry and ventilated indoor place to prevent the motor from getting damp; the fan stored in the open air shall be provided with protective measures to prevent rainwater and other sundries from entering the fan.

  2. For fans that have been stored for a long time, the rotating parts of the fans shall be derusted every month and coated with antirust oil to prevent rusting.

  3. The fan blades shall be cleaned regularly to extend the service life of the fan.

  4. Before starting the fan, make sure that the ventilation device at the inlet and outlet of the ventilation system is in the open state, so as to avoid the fan motor being burned due to the long-term back pressure.

  5. In case of abnormal sound, serious heating of motor, electrified shell, tripping of switch, etc. during the operation of the fan, the fan shall be shut down immediately for inspection. Restart the machine after confirming that there is no error.

  6. The use environment of the fan should always be kept clean, the surface of the fan should be kept clean, the inlet and outlet of the ventilation system should be free of sundries, and the dust and other sundries in the fan and the pipeline should be removed regularly. If there is an air filter, it should be cleaned regularly.

  7. According to the use environment and the actual situation, supplement or replace the wet wheel grease for the bearing irregularly.

Installation diagram Please click to download the detailed size drawing

Pay attention to the public number Get the extraction code.

ZYF-4A-All向-模型.png

Fan performance selection parameter table

ZYF-4AP=1.2kg/m3T=20℃
Pa219921002042189917711750160015051660rpm
m3/h25203240354041404560462049805160
Kw3.1 3.3 3.4 3.5 3.6 3.7 3.8 3.9 
Pa197618871835170715921572143813521570rpm
m3/h23893071335639244323437947214886
Kw2.9 3.2 3.3 3.5 3.5 3.6 3.7 3.8 
Pa181117301682156514591441131812481480rpm
m3/h22872941321337584139419345204678
Kw2.3 2.4 2.5 3.0 3.1 3.2 3.3 3.4 
Pa166515851541143313371320120711451410rpm
m3/h21792815307535973962401443264468
Kw2.0 2.1 2.2 2.7 2.8 2.9 3.0 3.1 
Pa150814401400130312151198109710401340rpm
m3/h20802683293234283776382641244273
Kw1.5 1.8 2.1 2.3 2.4 2.5 2.6 2.7 
Pa1370130412711182110210859969421260rpm
m3/h19882556279332663597364539294071
Kw1.3 1.5 1.6 2.1 2.2 2.3 2.4 2.5 
Pa124411881155107410029909058511180rpm
m3/h18952437266231143430347537453881
Kw1.1 1.3 1.4 1.5 1.6 1.7 1.8 1.9 


image.png